Suzhou Transfer X Co., Ltd.

Model: T121

Loop-powered isolated temperature transmitter for RTD, TC, mV, Ohm
T121 is a high-precision temperature transmitter designed for head-mounted installation, suitable for machinery, factories, installations and process industries. It is intended to shorten measurement time, reduce debugging and maintenance costs. This device converts input signals from Cu50, Cu100, Pt100, Pt500, Pt1000, Ni100, Ni120, Ni1000, TC probes (J, K, R, S, T, B, E, N, L), potentiometers, and mV into current normalized signals through a 4..20 mA loop (2-wire technology) with 16-bit resolution. The key features of this transmitter are its wide operating temperature range (-40…85°C), small size, quick connection via push-in spring terminals, and 2-channel current isolation between input and output to ensure data integrity. T121 has been certified for ATEX II 3G Ex nA IIC T4 Gc X (gas) and II 3D Ex tc IIIC T135°C Dc X (dust). All parameters can be configured using a Windows software through a USB->UART TTL converter (such as EASY USB or S117P1 converter (USB->RS232, RS485, UART TTL)).
 

 

power supply7..30 Vdc (Loop Power Supply)
quarantine1.5KVAC
response time<1 second
accuracy class0.1% (minimum RTD temperature of 0.1°C, minimum TC temperature of 1°C)
input typeCu50, Cu100
, Pt100, Pt500, Pt1000,
Ni100, Ni120, Ni1000
, TC, J, K, R, S, T, B, E, N, L; Input impedance 10 MΩ
Potentiometer: 500 Ω..100 kΩ
Voltage: -150.. +150 mV; Input impedance: 10 MΩ
Resistor: 0..+400 (1,760) Ω
Output typeCurrent (mA)
4..20, 20..4 mA (2-wire)
configurationEASY SETUP software (startup/full scale, suppression, RTD type, cable resistance, over-range, etc.)
operating temperature-40..+85°C
connectclip
Size (Ø x H)Diameter: 43.7 x 20 millimeters
authenticationCE and ATEX certifications
ruleEN 61000-6-4、EN 61000-6-2
Contact Us
Company Brands
social media
department store
look for sth.

Suzhou Transfer X Co., Ltd.
Address: No.26, Nanyangli, Gusu District, Suzhou, China
Tel: 0512-80197319
E-mail: service@transferx.cn